Category of: Electric actuator
Product Name: Lunar Phase Series Electric Actuator
Product introduction:
The lunar phase series electric actuator in the automatic adjustment system according to the adjustment instrument signal change perform 0 ~ 180° or 0 ~ 360° rotation to drive the valve to control the opening.
Powered by alternating current or direct current it can directly receive digital signals from computer or instrument 4-20madc or 1-5vdc standard analog signals to realize intelligent control and accurate positioning of electric valves.
Electric actuator and accessories with double limit overload overheating protection good safety performance.A variety of speeds are available for full travel time.
Various Angle stroke valves (ball valve butterfly valve plug valve etc.) and valves together constitute electric control valve electric ball valve electric butterfly valve and other industrial automatic electric valves.
Electronic actuators for precise position control and modulation applications
Control type:
On/Off type
|
Regulation type
|
|
|
On/Off
|
A built-in control module can control by PLCDCS system via
4-20mA or 0-10V analog signal
regulation precision can be 300:1
|
Type
|
20
|
50
|
100
|
|
Output torque
|
20NM
|
50NM
|
100NM
|
|
Action time
|
15S
|
15S/30S
|
15S/30S
|
|
Gyration angle
|
0-180°
0-360° |
0-180°
0-360° |
0-1800°
0-360° |
|
Motor power
|
AC220V
|
6W
|
10W
|
25W
|
AC380V
|
-
|
6W
|
15W
|
|
DC24V
|
8W
|
13W
|
25W
|
|
Rated current
|
AC220V
|
0.16A
|
0.16A
|
0.32A
|
AC380V
|
-
|
0.07A
|
0.10A
|
|
DC24V
|
0.7A
|
1.28A
|
2.03A
|
|
Weight
|
1.2Kg
|
2.5kg
|
3.5kg
|
|
Suited valve
|
Ball valve
|
DN15
|
DN15-40
|
DN50-65
|
Butterfly valve
|
-
|
DN32-50
|
DN50-125
|
|
Power supply
|
AC220V / AC380V / DC24V / AC110V / DC220V
|
|||
Modulation accuracy | Hystersis≤0.5% Dead band≤0.5% Feedback error≤0.5% | |||
Isolation resistance
|
100MΩ/500VDC
|
|||
Withstand Voltage
|
1500VAC 1min
|
|||
Protection
level |
IP68(No leakage in 20m deep water)
|
|||
Limited component
|
●Power driven:Fully open and closelimit switch |
|||
Protector
|
Overheat protector (Self-recovery)
|
|||
Installation position
|
Any direction from 0 to 360 degree |
|||
Electrical connection
|
M20*1.5 Waterproof cable connection power wire signal wire
|
|||
Ambient Temp.
|
-30℃--60℃
|
|||
Inspection standard |
JB/T8219-1999
|
Optional function | Code |
▲Torque limiter | ATS |
▲Bracket and shaft sleeve | ZT |
▲Remote control | C |
▲Dehumidifying heater | H |
Stem direct-connected diagram (Refer to ISO5211)
Direct-connected type-EA-20
|
Direct-connected type-EA-50
|
|
|
Direct-connected type-EA-100
|
|
Model |
Circuit |
Model |
Circuit |
S |
ON/OFFno output signal |
CPT |
ON/OFFoutput 4~20mA signal |
MS |
ON/OFFoutput passive contact signal |
PCU |
Regulationoutput 4~20mA signal |
PIU |
ON/OFFoutput 0~1000Ω signal |
G |
ON/OFFoutput passive contact signal |
SP |
ON/OFFmiddle position control |
H |
ON/OFFoutput passive contact signal |
Leading manufacturer of industrial automation equipment